  "title": "De-energize, Test, Lockout/Tagout",
  "description": "Learn which test equipment verifies a de-energized circuit, why OFF switches and indicator lights are not proof, and where qualified-person and LOTO boundaries apply.",
  "kind": "lesson",
  "safetyNotice": "Learning reference only: electrical codes, permits, inspection bodies, and licensing rules differ by region. This course is not a substitute for local code, licensed training, permits, or authority requirements. Before any hands-on work, de-energize, verify absence of voltage, and follow local regulators/AHJ and employer procedures.",
  "sections": [
    {
      "id": "deenergized-test-equipment",
      "heading": "What tool indicates if a system is de-energized?",
      "paragraphs": [
        "An appropriately rated voltage-testing instrument is used as part of a qualified person's verification procedure. A switch in the OFF position, a dark indicator or a continuity beep is not sufficient evidence of a de-energized system.",
        "For US electrical work within its scope, OSHA 1910.333(b)(2)(iv) requires verification at the circuit elements and equipment parts to which workers will be exposed, including possible backfeed or induced voltage. Learn the terminology here; actual verification follows local rules, equipment instructions and an employer's procedure."
      ],
      "links": [
        {
          "title": "OSHA 1910.333 — verification of deenergized condition",
          "url": "https://www.osha.gov/laws-regs/regulations/standardnumber/1910/1910.333"
        },
        {
          "title": "OSHA interpretation — an indicator light is not deenergization test equipment",
          "url": "https://www.osha.gov/laws-regs/standardinterpretations/2012-12-12"
        },
        {
          "title": "Multimeter symbols, modes and readings",
          "url": "https://elect-learn.org/en/guides/multimeter-symbols/"
        },
        {
          "title": "Lockout/tagout language and roles",
          "url": "https://elect-learn.org/en/guides/lockout-tagout-english-vocabulary/"
        }
      ]
    },
    {
      "id": "section-1",
      "heading": "Lesson information",
      "paragraphs": [
        "Safety and Tools · Beginner · 20 min",
        "LOTO",
        "Verification"
      ]
    },
    {
      "id": "section-2",
      "heading": "Disconnect, secure, verify.",
      "paragraphs": [
        "Switching off is an action; proving dead is a verification. A lock prevents re-energization, while testing establishes the present state."
      ],
      "items": [
        "Identify all energy sources, including backfeeds.",
        "Follow the authorized isolation and lockout procedure; address stored energy.",
        "A qualified person verifies absence of voltage and proves the tester before and after."
      ]
    },
    {
      "id": "section-3",
      "heading": "Goals",
      "items": [
        "Understand how LOTO prevents unexpected energization or startup.",
        "Learn live-dead-live verification logic.",
        "Know learners can simulate the workflow, while field execution must follow employer and local rules."
      ]
    },
    {
      "id": "section-4",
      "heading": "A coworker re-energizes the breaker",
      "paragraphs": [
        "During light fixture maintenance, someone sees a breaker off and turns it back on.",
        "Wrong call: Relying on a verbal warning with no clear control of the energy source.",
        "Stop point: Shared areas or workplaces require procedural locking and identification.",
        "Reasoning path: Identify all sources, notify affected people, isolate, lock/tag, verify absence, then restore through procedure.",
        "Review: OSHA LOTO emphasizes employer procedures, training, authorized employees, and hazardous energy control."
      ]
    },
    {
      "id": "section-5",
      "heading": "Core concepts",
      "items": [
        "De-energizing is not a guess; it isolates energy sources from equipment.",
        "Verification proves the tester works, proves the target is de-energized, then proves the tester still works.",
        "The core of lockout/tagout is preventing others from restoring energy."
      ]
    },
    {
      "id": "tool-multimeter",
      "heading": "Digital Multimeter",
      "paragraphs": [
        "Measures voltage, continuity, and resistance so you verify instead of guess.",
        "Misuse and limits: Wrong jack or mode selection can damage the meter or create danger."
      ]
    },
    {
      "id": "tool-tester",
      "heading": "Non-contact Voltage Tester",
      "paragraphs": [
        "Quickly screens for possible voltage as an early warning.",
        "Misuse and limits: It is not proof of absence of voltage by itself; confirm with a suitable meter."
      ]
    },
    {
      "id": "tool-driver",
      "heading": "Insulated Screwdriver",
      "paragraphs": [
        "Used for terminals and cover screws; insulation adds a layer of protection.",
        "Misuse and limits: An insulated tool is not permission for live work and must not be trusted if damaged."
      ]
    },
    {
      "id": "section-9",
      "heading": "Common Pitfalls",
      "items": [
        "Turning a breaker off without preventing re-energization.",
        "Trusting an unverified tester as the final answer.",
        "Ignoring multiple sources or stored energy."
      ]
    },
    {
      "id": "section-10",
      "heading": "Safe Workflow",
      "items": [
        "Write down the target equipment and possible sources.",
        "Shut off and isolate the correct source, then lock/tag according to local and employer procedure.",
        "Verify with a live-dead-live sequence.",
        "After work, account for tools and people before restoring through procedure."
      ],
      "ordered": true
    },
    {
      "id": "quiz-1",
      "heading": "Why test a known live point first?",
      "paragraphs": [
        "To confirm the meter, leads, and settings work; otherwise a zero reading may be a tool problem."
      ]
    },
    {
      "id": "quiz-2",
      "heading": "What main risk does LOTO prevent?",
      "paragraphs": [
        "Unexpected startup or re-energization during servicing or maintenance."
      ]
    },
    {
      "id": "section-13",
      "heading": "Look Back",
      "links": [
        {
          "title": "Review Lesson 1: why absence of voltage cannot be assumed.",
          "url": "https://elect-learn.org/en/lesson/01-why-electricity-is-dangerous/"
        }
      ]
    }
  ],
  "dateModified": "2026-10-27",
  "publisher": {
    "name": "Elect Learn",
    "url": "https://elect-learn.org"
  },
  "review": {
    "status": "not-independently-reviewed",
    "statement": "No independent professional review is recorded. Cited sources do not imply review or endorsement by those organizations.",
    "policyUrl": "https://elect-learn.org/en/methodology/"
  }
}