  "title": "Series, Parallel, Loads, and Voltage Drop",
  "description": "Understand why residential loads are usually parallel, and why voltage drop or loose connections cause symptoms.",
  "kind": "lesson",
  "safetyNotice": "Learning reference only: electrical codes, permits, inspection bodies, and licensing rules differ by region. This course is not a substitute for local code, licensed training, permits, or authority requirements. Before any hands-on work, de-energize, verify absence of voltage, and follow local regulators/AHJ and employer procedures.",
  "sections": [
    {
      "id": "series-load",
      "heading": "What is a series load?",
      "paragraphs": [
        "A series load is a load connected in the same single current path as another component. In an ideal series circuit the current is the same through each element, and the supply voltage is shared across them. Parallel branches connect across the same two nodes and share the same voltage in the ideal model."
      ],
      "question": "Two 10 Ω resistors are in series across an ideal 12 V source. What is the current, and the voltage across each resistor?",
      "answer": "Total resistance is 20 Ω, so I = 12 / 20 = 0.6 A. Each resistor has 0.6 × 10 = 6 V across it. This is a paper calculation, not a component-selection or wiring instruction.",
      "links": [
        {
          "title": "Electrical symbols chart and circuit practice",
          "url": "https://elect-learn.org/en/guides/electrical-drawing-symbols/"
        },
        {
          "title": "Check an ideal Ohm's law calculation",
          "url": "https://elect-learn.org/en/tools/ohms-law-calculator/"
        }
      ]
    },
    {
      "id": "section-1",
      "heading": "Lesson information",
      "paragraphs": [
        "Circuit Fundamentals · Basic · 20 min",
        "Loads"
      ]
    },
    {
      "id": "section-2",
      "heading": "Same loads. What changes with the connection?",
      "paragraphs": [
        "Keep the source and resistances unchanged; change only the connections to compare total current and load voltage."
      ],
      "items": [
        "Series components share one path and the same current.",
        "Ideal parallel branches share a voltage; branch currents add.",
        "Real conductors have resistance; drop rises with current and line resistance."
      ]
    },
    {
      "id": "section-3",
      "heading": "Goals",
      "items": [
        "Distinguish series and parallel load behavior.",
        "Understand voltage drop depends on length, current, and connection quality.",
        "Connect heating with loose connections."
      ]
    },
    {
      "id": "section-4",
      "heading": "Lights dim when a far-end tool starts",
      "paragraphs": [
        "A saw starts from a far garage receptacle and nearby lights dim noticeably.",
        "Wrong call: Assuming it is fine because the tool runs.",
        "Stop point: Stop if there is persistent heat, odor, sparking, or repeated trips.",
        "Reasoning path: Check load current, conductor length, connection points, circuit capacity, and whether a dedicated circuit is needed.",
        "Review: Exam focus: parallel circuits, voltage drop, connection resistance, and overload."
      ]
    },
    {
      "id": "section-5",
      "heading": "Core concepts",
      "items": [
        "Parallel wiring lets each load receive approximately full supply voltage.",
        "Conductors have resistance; high current and long distance increase voltage drop.",
        "A loose connection acts like extra resistance, causing heat and intermittent faults."
      ]
    },
    {
      "id": "tool-multimeter",
      "heading": "Digital Multimeter",
      "paragraphs": [
        "Measures voltage, continuity, and resistance so you verify instead of guess.",
        "Misuse and limits: Wrong jack or mode selection can damage the meter or create danger."
      ]
    },
    {
      "id": "tool-wire-nut",
      "heading": "Wire Connector",
      "paragraphs": [
        "Mechanically joins and insulates compatible conductors.",
        "Misuse and limits: Wrong size, uneven copper, or no pull test can leave a loose splice."
      ]
    },
    {
      "id": "tool-cable",
      "heading": "NM Cable / Conductors",
      "paragraphs": [
        "Carries circuit current; color and markings help identify use.",
        "Misuse and limits: Wrong gauge, jacket, environment, or color use may violate code."
      ]
    },
    {
      "id": "section-9",
      "heading": "Common Pitfalls",
      "items": [
        "Blaming all dimming on the lamp itself.",
        "Ignoring loose terminals or poor wire connector splices.",
        "Using extension cords as long-term fixed wiring."
      ]
    },
    {
      "id": "section-10",
      "heading": "Safe Workflow",
      "items": [
        "Record whether the symptom appears only when a large load starts.",
        "After de-energizing, inspect visible connections for discoloration, looseness, or heat marks.",
        "Have licensed personnel handle rewiring or new circuits through the permit process."
      ],
      "ordered": true
    },
    {
      "id": "quiz-1",
      "heading": "Are residential receptacles usually supplied in series or parallel?",
      "paragraphs": [
        "Parallel, so each load receives approximately full supply voltage."
      ]
    },
    {
      "id": "quiz-2",
      "heading": "Why is a loose connection dangerous?",
      "paragraphs": [
        "It adds contact resistance, which can heat, arc, and cause intermittent failures."
      ]
    },
    {
      "id": "section-13",
      "heading": "Look Back",
      "links": [
        {
          "title": "Review Lesson 4: higher current increases heating concerns.",
          "url": "https://elect-learn.org/en/lesson/04-voltage-current-power/"
        },
        {
          "title": "Review Lesson 5: load current travels hot and neutral.",
          "url": "https://elect-learn.org/en/lesson/05-hot-neutral-ground/"
        }
      ]
    }
  ],
  "dateModified": "2026-10-23",
  "publisher": {
    "name": "Elect Learn",
    "url": "https://elect-learn.org"
  },
  "review": {
    "status": "not-independently-reviewed",
    "statement": "No independent professional review is recorded. Cited sources do not imply review or endorsement by those organizations.",
    "policyUrl": "https://elect-learn.org/en/methodology/"
  }
}